2015-05-07 12:40:02 | 5/7/2015 |
| PROJECT: KITCHEN REMODEL |
| PERMIT#: 15050180 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) NEC 210.52(A) |
| VERIFY RECEPTACLE SPACING. THERE APPEAR TO BE WALLS IN |
| NEED OF RECEPTACLES TO MEET THIS MINIMUM REQUIREMENT. |
| |
| 2) WPB AMENDMENTS TO FBC 107.3.5.1.2 |
| PROVIDE ADDITIONAL DETAIL TO SUPPORT THE RELOCATION OF |
| THE BREAKER PANEL INCLUDING HOW ALL EXISTING BRANCH |
| CIRCUITS WILL BE RELOCATED. PROVIDE A DESIGN DETAIL |
| ILLUSTRATING METHODS AND MATERIALS PROPOSED. |
| |
| 3) NEC 210.8(6) |
| ALL ALL OUTLETS IN THE KITCHEN SHALL HAVE GFI |
| PROTECTION FOR PERSONELL. |
| |
| 4) PROVIDE DIMENSIONS FOR NEW LOCATION OF PANELBOARD TO |
| SHOW COMPLIANCE WITH THE NEC 110.26 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |