Plan Review Notes
Plan Review Notes For Permit 15050178
Permit Number 15050178
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-29 11:00:45THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. THESE PLANS FAIL TO PROPERLY DEFINE THE SCOPE OF
 WORK.
 2. THE RISER DIAGRAM INDICATES THAT ONLY THREE (3) NEW
 DEVICES ARE BEING INSTALLED
 3. AS PART OF THE NEW DEVICES BEING INSTALLED, A NEW
 SMOKE DETECTOR IN THE ELECTRIC ROOM WHICH SHOULD HAVE
 ALREADY HAD ONE THERE. CHECK THE DEVICE PLACEMENT AS
 SHOWN ON THE PLANS WITH THE ACTUAL SCOPE OF WORK. AND
 CORRECT THE DRAWINGS ACCORDINGLY.
 I SPOKE WITH MICHAEL COTTIERO OF KNIGHT FIRE & SECURITY
 ON THIS OVER THE PHONE.
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-7943
 EMAIL: [email protected]
  