Plan Review Notes For Permit 15050178 |
Permit Number |
15050178 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-29 11:00:45 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR A SECOND REVIEW: | | 1. THESE PLANS FAIL TO PROPERLY DEFINE THE SCOPE OF | | WORK. | | 2. THE RISER DIAGRAM INDICATES THAT ONLY THREE (3) NEW | | DEVICES ARE BEING INSTALLED | | 3. AS PART OF THE NEW DEVICES BEING INSTALLED, A NEW | | SMOKE DETECTOR IN THE ELECTRIC ROOM WHICH SHOULD HAVE | | ALREADY HAD ONE THERE. CHECK THE DEVICE PLACEMENT AS | | SHOWN ON THE PLANS WITH THE ACTUAL SCOPE OF WORK. AND | | CORRECT THE DRAWINGS ACCORDINGLY. | | I SPOKE WITH MICHAEL COTTIERO OF KNIGHT FIRE & SECURITY | | ON THIS OVER THE PHONE. | | | | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 | | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE | | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA | | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND | | FLORIDA BUILDING CODE ENERGY CONSERVATION. | | | | FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT: | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | PH: (561) 805-7943 | | EMAIL: [email protected] | | |
|