2015-08-18 14:12:15 | 3RD REVIEW: FBC 2010 MECHANICAL | | PERMIT #15050177 | | 8/18/15 | | | | 1) THE REVISED ENERGY CALCULATIONS MUST BE SIGNED AND | | DATED BY THE PERSON WHO PREPARED THEM- | | SECTION103.2.3.1.2 FBC-10- ENERGY CONSERVATION. | | 2) SHEET M-1: AS PREVIOUSLY REQUESTED PROVIDE THE | | VENTILATION CALCULATION AND OUTSIDE AIR CFM'S FOR THE | | VIP AREA. CORRECT THE TOTAL CFM'S OF O/A FOR THE OFFICE | | TO 33 CFM'S. | | 3) AS PREVIOUSLY REQUESTED PROVIDE THE NOA OR FLORIDA | | PRODUCT APPROVAL FOR THE O/A LOUVER. | | 4) PROVIDE MANUFACTURER'S SPECIFICATIONS AND | | INSTALLATION INSTREUCTIONS FOR THE AREA SMOKE | | DETECTORS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|