2015-07-21 06:00:13 | 1) SUBMIT A NARRATIVE THAT CLEARLY REFLECTS THE SCOPE |
| OF UNPERMITTED WORK THAT WAS DONE AND THE SCOPE OF WORK |
| TO CORRECT THE VIOLATION.WPB AMEND. TO FBC SEC. 107.1, |
| 107.2.1. 2ND REQUEST. |
| 2) CLEARLY SHOW ON THE PLANS THE ENTIRE SCOPE OF |
| PLUMBING WORK TO BE DONE.WPB AMEND. TO FBC SEC.107.2.1. |
| 3) PAGE 1 - CLEARLY SHOW THE WIDTH OF THE TOILET ROOMS. |
| THE LAVATORY SHALL NOT ENCROACH INTO THE CLEAR FLOOR |
| SPACE FOR THE WATER CLOSET.FAC 604.3.1. |
| 4) SHOW THE FIXTURE CLEARANCE OF THE HANDICAP WATER |
| CLOSET FROM THE NEAREST ADJACENT FINISHED WALL TO THE |
| CENTERLINE OF THE WATER CLOSET.COMPLY WITH FGURE 604.2 |
| IN THE FAC. |
| 5) SHOW THE LOCATION OF THE CONTROL WALL FOR THE |
| HANDICAP SHOWERS ON SHT.#1. |
| 6) THE SHOWER IN THE LOCKER ROOM DOES NOT APPEAR TO |
| SUPPLY THE 36" |
| X 48" CLEAR FLOOR SPACE ADJACENT TO THE SHOWER. FAC |
| SEC.608.2.1. |
| 7) THE RESTROOMS ARE NOT SHOWN ON THE SANITARY OR WATER |
| RISERS. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 8) LABEL THE FIXTURES ON THE WATER RISER. WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 9) THE SANITARY RISER AND THE WATER RISER DOES NOT |
| CORRELATE WITH THE FLOOR PLAN. WPB AMEND. TO FBC SEC. |
| 107.5.1.3. |
| 10) THE ENTIRE HOT AND COLD WATER LINES ARE PIPED IN |
| 1/2 " PIPE. SUBMIT CALCULATIONS THAT THIS SIZING WILL |
| SUPPLY THE MINIMUM FLOW RATES AND PRESSURES REQUIRED AT |
| EACH FIXTURE PER TABLE 604.3 OF 2010 FPC. |
| 11) THE PLANS NOTE AN OCCUPANCY OF A-2 AND A OCCUPANT |
| LOAD OF 267 PERSONS. TABLE 403.1 OF THE 2010 FL. PLBG. |
| CODE WOULD REQUIRE 4 WATER CLOSETS FOR THE MALES AND 4 |
| WATER CLOSETS FOR THE FEMALES. |
| 12) INDICATE THE PREVIOUS OCCUPANCY OF THIS SPACE PER |
| CHAPTER 302 OF THE 2010 FBC. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |