2015-07-10 11:10:02 | 2ND REVIEW: FBC 2010 MECHANICAL |
| PERMIT #1505177 7/10/15 |
| |
| 1) THE ENERGY EFFICIENCY FORM IS LISTING TWO 13 SEER |
| SYSTEMS, AND ONE 10 SEER SYSTEM WHICH IS NOTED ON THE |
| FORM AS A FAILED COMPLIANCE, HOWEVER THE PLAN IS |
| INDICATING THREE 16 SEER SYSTEMS: PLEASE CORRECT. |
| 2) SHEET M-1: THE 24X24 INCH RETURN GRILL IS UNDERSIZED |
| FOR 1600 CFM PER SECTION 601.4 (50 SQ. INCHES PER 100 |
| CFM REQUIRED- MINIMUM GRILL SIZE IS APPROXIMATELY 28 X |
| 28 SQ. INCHES). PLEASE NOTE THAT THE PLANS DO NOT SHOW |
| WHAT THE GRILL IS TO BE MOUNTED TO- A DOOR AT THE FRONT |
| OF THE CLOSET IS NOT SHOWN ON THE PLANS. |
| 3) M-1: INDICATE HOW ACCESS FOR SERVICE IS BEING |
| PROVIDED TO AHU-1 & 3 EACH LOCATED ABOVE THE DROP |
| CEILINGS, AND SHOW THE LEVEL 30 X 30 INCH LEVEL WORKING |
| SPACE IN FRONT OF THE CONTROL SIDES OF THE UNITS- |
| REFERENCE SECTION 306.1. |
| 4) M-1: THE ASHRAE 62- 89 VENTILATION CALCULATIONS |
| SHOWN ON THE PLAN ARE OUTDATED. REVISE THE CALCULATIONS |
| AS PREVIOUSLY REQUESTED USING TABLE 403.3. A) |
| BAR/LOUNGE- 7.5 CFM PER PERSON PLUS .18 CFM PER SF. B) |
| STORAGE- .12 CFM PER SF. C) OFFICE- 5 CFM PER |
| PERSON/.06 CFM PER SF. D) STAGES- 10 CFM PER PERSON/.06 |
| CFM PER SF. E)THE LOCKER/SHOWER ROOM REQUIRES EXHAUST |
| RATES OF 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS FOR |
| THE SHOWER, AND .25 CFM PER SF FOR THE ROOM ITSELF. F) |
| AN ACCURATE CALCULATION FOR THE VIP ROOM WILL DEPEND ON |
| THE TYPE OF ACTIVITY CONDUCTED IN THE SPACE. |
| 5) M-1: THERE ARE SD SYMBOLS SHOWN AT THE RETURNS OF |
| THE THREE AIR HANDLERS. PLEASE CLARIFY IF THESE ARE |
| MEANT TO BE DUCT SMOKE DETECTOR SYMBOLS (DS), AND |
| CLARIFY HOW THEY WILL BE SUPERVISED PER SECTION |
| 606.4.1. PLEASE NOTE THAT DETECTORS SHALL BE INSTALLED |
| IN SUPPLY SYSTEMS WITH A DESIGN CAPACITY GREATER THAN |
| 2000 CFM- 606.2.1 |
| 6) M-1: AS PREVIOUSLY REQUESTED PROVIDE DUCT HANGING |
| AND CONNECTION DETAILS, INCLUDING THE DISTRIBUTION |
| BOXES- CHAPTER 5- SMACNA 2005. |
| 7) M-1: SOME DUCT SIZES ARE STILL NOT SHOWN IN THE REAR |
| CORRIDOR AND VIP ROOM: PLEASE LIST THESE SIZES AND THE |
| DB SIZES. |
| 8) M-1: A DUCT CONNECTION BETWEEN THE R/A GRILL IN THE |
| CORRIDOR AND A SUPPLY DIFFUSER IN THE OFFICE IS SHOWN |
| ON THE PLAN: PLEASE CORRECT. |
| 9) M-1: PLEASE ENLARGE THE DRYWELL DETAIL FOR CLARITY. |
| 10) AS PREVIOUSLY REQUESTED, PROVIDE TWO COPIES OF FL. |
| PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR THE O/A |
| INTAKE LOUVERS, AND FOR THE AST AC STAND REVIEWED AND |
| APPROVED BY THE DESIGN PROFESSIONAL OF RECORD- DCA RULE |
| 9N-03. |
| |