Plan Review Notes
Plan Review Notes For Permit 15050177
Permit Number 15050177
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-22 14:03:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050177
 ADD: 1152 OKEECHOBEE RD
 CONT: ABACOA CONSTRUCTION
 TEL: (561)722-3890
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WEDNESDAY JULY 22/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) THE PLATFORM DOES INDICATEVERTICAL ACCESSIBILITY
 WILL BE ACHIEVED BY A PLATFORM LIFT. , PLEASE PROVIDE
 COMPLIANCE WITH THE 2010 FBC-ACCESSIBILITY CODE,
 201.1.1 VERTICAL ACCESSIBILITYSECTIONS 553.501-553.513,
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO
 NOT RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR
 FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER
 THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN
 SUCH BUILDING, STRUCTURE OR FACILITY. PLEASE PROVIDE
 THE MANUFACTURERS LIFT DESIGN CRITERIA.
  
 PLATFORM LIFTS ARE TO MEET THE ASME A18.1 STANDARDS.
 PLEASE SHOW COMPLIANCE WITH 410 PLATFORM LIFTS:
  
 410.1 GENERAL.
 PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1 (1999
 EDITION OR 2003 EDITION) (INCORPORATED BY REFERENCE,
 SEE ?REFERENCED STANDARDS? IN CHAPTER 1). PLATFORM
 LIFTS SHALL NOT BE ATTENDANT-OPERATED AND SHALL PROVIDE
 UNASSISTED ENTRY AND EXIT FROM THE LIFT.
  
 410.2 FLOOR SURFACES.
 FLOOR SURFACES IN PLATFORM LIFTS SHALL COMPLY WITH 302
 AND 303.
  
 410.3 CLEAR FLOOR SPACE.
 CLEAR FLOOR SPACE IN PLATFORM LIFTS SHALL COMPLY WITH
 305.
  
 410.4 PLATFORM TO RUNWAY CLEARANCE.
 THE CLEARANCE BETWEEN THE PLATFORM SILL AND THE EDGE OF
 ANY RUNWAY LANDING SHALL BE 1 INCH (32 MM) MAXIMUM.
  
 410.5 OPERABLE PARTS.
 CONTROLS FOR PLATFORM LIFTS SHALL COMPLY WITH 309.
  
 410.6 DOORS AND GATES.
 PLATFORM LIFTS SHALL HAVE LOW-ENERGY POWER-OPERATED
 DOORS OR GATES COMPLYING WITH 404.3. DOORS SHALL REMAIN
 OPEN FOR 20 SECONDS MINIMUM. END DOORS AND GATES SHALL
 PROVIDE A CLEAR WIDTH 32 INCHES (815 MM) MINIMUM. SIDE
 DOORS AND GATES SHALL PROVIDE A CLEAR WIDTH 42 INCHES
 (1065 MM) MINIMUM.
  
 5-7) COMPLIED.
  
 8) 2ND REQUEST. SHEET LS-1 THE DOOR SCHEDULE SHOWS DOOR
 TYPE 1 TO BE A 2'-8" DOORS ARE TO COMPLIANCE FOR FBC-B
 1008.1.1 AND ACCESS. CODE 404.2.3.
  
 9) SHEET LS-1 THE PLANS INDICATES THE STORAGE ROOM TO
 BE 425 SQ. FT. THE OVERALL TOTAL SQUARE FOOTAGE GIVEN
 IS 4,000 SQ. FT. OR OVER 10 % OF THE FLOOR AREA THAT
 CREATES A MIXED USE OCCUPANCY. SEE 2010 FBC-B 508.2.1
 AREA LIMITATIONS. PLEASE REVIEW THE 2010 FBC-B TABLE
 508.4 DEPENDING IF THE STORAGE ROOM IS A S1 OR S2 THE
 ROOM WILL REQUIRE A 1 HR OR 2 HOUR FIRE SEPARATION, NO
 FIRE SPRINKLERS.
  
 10) THE MECHANICAL PLANS (M1) ALSO SHOW WALL LOUVERS
 AND ROOF TOP A/C STANDS. PLEASE PROVIDE COMPLIANCE
 WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS- OUTSIDE AIR
  
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved