2015-06-03 14:28:30 | 1) THE PLANS ARE UNCLEAR AS TO THE LEVEL AND SCOPE OF |
| INTERIOR ALTERATIONS BEING DONE. SUBMIT A NARRATIVE |
| THAT CLEARLY REFLECTS THE SCOPE OF UNPERMITTED WORK |
| THAT WAS DONE AND THE SCOPE OF WORK TO CORRECT THE |
| ISSUE. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 2) CLEARLY SHOW ON THE PLANS THE SCOPE OF WORK TO BE |
| DONE. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 3) THE DESIGN PROFESSIONAL SHALL INDICATE ON THE PLANS |
| THE LEVEL OF ALTERATION OF THE WORK PER THE FL. |
| EXISTING BUILDING CODE SEC.401.4. |
| 4) CLEARLY INDICATE THE WORK AREA ON THE PLANS PER THE |
| FL. EXISTING BUILDING CODE SEC. 401.2. |
| 5) PAGE 1 - CLEARLY INDICATE THE WIDTH OF THE TOILET |
| ROOMS. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 6) SHT. OC-1 - HOW CAN THE BAR AREA BE DESIGNATED AS A |
| BUSINESS OCCUPANCY? THIS AREA IS AN A-2 AND SHALL BE |
| INCLUDED IN THE A-2 OCCUPANT LOAD COUNT. 201 FBC 303. |
| 7) A BUILDING, FACILITY OR ELEMENT THAT IS ALTERED |
| SHALL COMPLY WITH THE PROVISIONS OF THE FBC- |
| ACCESSIBILITY. REFER TO FL. ACCESSIBILITY CODE SEC. 202 |
| FOR ALTERATIONS TO AN EXISTING BUILDING. |
| 8) SUBMIT PLUMBING PLANS FOR ANY CHANGES TO THE |
| SANITARY OR WATER SYSTEM.WPB AMEND. TO 2010 FBC SEC. |
| 107.2.1. |
| 9) SHT. LS-1 - PLEASE PROVIDE DIMENSIONS FOR ALL |
| RESTROOMS AND SHOWER STALLS TO REVIEW FOR REQUIRED |
| COMPLIANCE WITH THE FAC. PROVIDE ENLARGED FLOOR PLANS & |
| ELEVATIONS OF BATHROOMS & SHOWERS. SHOW FLOOR |
| CLEARANCES FOR PLUMBING FIXTURES, PLUMBING FIXTURE |
| CLEARANCES, GRAB BARS HEIGHTS, ETC. |
| |
| NOTE: DUE TO LACK OF INFORMATION ON THE PLANS AS TO THE |
| EXTENT OF THE ALTERATIONS, THIS IS NOT A COMPREHENSIVE |
| REVIEW. MORE COMMENTS MAY BE GENERATED ONCE A COMPLETE |
| SET OF PLANS IS SUBMITTED. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |