2015-06-03 17:49:311ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE AC LOAD CALCULATIONS IN ACCORDANCE WITH
 ASHRAE/ACCA STANDARD 183, OR ACCA MANUAL N FOR THE NEW
 SYSTEMS- SECTION 503.2.1 FBC-10 ENERGY CONSERVATION.
 2) PROVIDE VENTILATION CALCULATIONS FOR THE A2
 OCCUPANCY INCLUDING A TABLE DEPICTING THE REQUIRED AND
 PROVIDED O/A OR EXHAUST FOR EACH ROOM OR SPACE ON THE
 PLAN- TABLE 403.3 FBC-10 MECHANICAL.
 3) SHEET M-1: PLEASE INDICATE ALL THE DUCT SIZES ON THE
 PLAN: MANY ARE NOT INDICATED.
 4) PLEASE LABEL THE AIR HANDLERS AS EITHER 1, 2, OR 3.
 5) M-1: SHOW THE OUTSIDE AIR INTAKE DUCTS FOR THE AHU'S
 SHOWN BY THE CONCESSION STAND, AND OVER THE MEN'S
 TOILET ROOM. INDICATE THE TYPE AND SIZE OF THE DUCTS,
 AIR INLET LOCATION, AND TYPE AND SIZE OF INLET GRILL OR
 LOUVER. PLEASE NOTE, TWO COPIES OF A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA WILL BE REQUIRED.
 6) M-1: PROVIDE MOTORIZED DAMPERS FOR THE OUTSIDE AIR
 INTAKES THAT WILL AUTOMATICALLY SHUT OFF WHEN THE
 SYSTEMS OR SPACES ARE NOT IN USE- SECTION 503.2.4.4
 FBC-10 ENERGY CONSERVATION.
 7) M-1: PROVIDE EXHAUST VENTILATION PLANS AND
 SPECIFICATIONS FOR THE TOILET ROOMS, INCLUDING EXHAUST
 FAN EQUIPMENT SCHEDULES, THE TYPE AND SIZE OF EXHAUST
 DUCTS, DUCT RUNS, AND TERMINATION LOCATIONS.
 8) M-1: INDICATE SUPPLY CFM'S AT THE 24 X 24 DIFFUSERS
 SHOWN ON THE PLAN AND THE LEGEND.
 9) M-1: PER DETAIL NO. 2 ON M-2, SHOW THE LOCATIONS OF
 ALL REQUIRED DUCT SMOKE DETECTORS, AND TEST STATIONS ON
 THE PLAN- SEE FIRE DEPARTMENT COMMENTS REGARDING THE
 REQUIRED FIRE ALARM SYSTEM.
 10) M-1: PROVIDE AN AIR DISTRIBUTION SCHEDULE ON THE
 PLAN INDICATING THE MAKES AND MODELS OF DIFFUSERS AND
 GRILLS. SHOW DUCT HANGING AND CONNECTION DETAILS.
 11) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR
 HANDLERS: SHOW THE TYPE AND SIZE OF PIPING, PIPING
 RUNS, AND DISCHARGE LOCATIONS- SECTION 307 FBC-10
 MECHANICAL.
 12) SITE SPECIFIC, WINDLOAD TIE-DOWN ENGINEERING IS
 REQUIRED FOR THE NEW CONDENSER STANDS ON THE ROOF-
 SECTION 301.12 FBC-10 MECHANICAL. PROVIDE DESIGN
 CRITERIA AND DESIGN PRESSURES ON THE PLANS.
  