Plan Review Notes For Permit 15050177 |
Permit Number |
15050177 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-11 19:07:00 | COMMENTSN AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | REVIEW | | PERMIT #: 15050177 | | DATE: 5/11/15 | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | CHAPTER 1; NEC 2008 | | REVIEW CYCLE: 1 | | ACTION: FAILED | | | | 1. PER FBC 907.2.1, GROUP A BLDGS W/AN OCCUPANT LOAD OF | | 300 OR GREATER ARE REQUIRED TO HAVE A FIRE ALARM SYSTEM | | INSTALLED (SEE FIRE REVIEW) | | 2. THE FIRE ALARM SYSTEM SHALL BE ON A SEPARATE PERMIT | | AND SUBMITTAL ACCOMPANIED BY THE PROPER FIRE ALARM | | DRAWINGS. | | 3, MISSING EXIT LIGHT IN STORAGE ROOM, LOCKER ROOM AND | | IN THE AREA MID-WAY AS YOU EXIT THE REAR AREA INTO THE | | LOUNGE. | | 4. OUTLETS BEHIND THE BAR, IF WITHIN 6' OF THE SINK | | SHALL BE GFI PROTECTED. | | 5. AS PER NEC 210.62, YOU ARE REQUIRED TO HAVE AN | | OUTLET AT THE TOP OF EVERY SHOW WINDOW FOR EVERY 12' OR | | FRACTION THEREOF. THIS OUTLET SHALL BE WITHIN 18" OF | | THE TOP OF THE WINDOW. | | 6.AS PER NEC 600.5, YOU ARE TO HAVE A DEDICATED SIGN | | OUTLET LOCATED ACCESSIBLE ABOVE EVERY ENTRANCE. | | 7. AS PER NEC 700.12(F) EMERGENCY LIGHTING SHALL BE ON | | THE SAME LIGHTING CIRCUIT AS THE AREA THEY OCCUPY. | | INDICATE LIGHTING CIRCUIT NUMBER TO ASCERTAIN | | COMPLIANCE. | | 8. AS PER FBC 2010 ENERGY 502.3.8, ALL RECESSED | | LIGHTING SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN | | CONDITIONED & UNCONDITIONED SPACE. | | 9. AS PER FBC 2010 ENERGY, ALL LIGHTING SHALL COMPLY | | WITH SECTION 505. | | |
|