2015-05-11 19:07:00COMMENTSN AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN
 REVIEW
 PERMIT #: 15050177
 DATE: 5/11/15
 APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010
 CHAPTER 1; NEC 2008
 REVIEW CYCLE: 1
 ACTION: FAILED
  
 1. PER FBC 907.2.1, GROUP A BLDGS W/AN OCCUPANT LOAD OF
 300 OR GREATER ARE REQUIRED TO HAVE A FIRE ALARM SYSTEM
 INSTALLED (SEE FIRE REVIEW)
 2. THE FIRE ALARM SYSTEM SHALL BE ON A SEPARATE PERMIT
 AND SUBMITTAL ACCOMPANIED BY THE PROPER FIRE ALARM
 DRAWINGS.
 3, MISSING EXIT LIGHT IN STORAGE ROOM, LOCKER ROOM AND
 IN THE AREA MID-WAY AS YOU EXIT THE REAR AREA INTO THE
 LOUNGE.
 4. OUTLETS BEHIND THE BAR, IF WITHIN 6' OF THE SINK
 SHALL BE GFI PROTECTED.
 5. AS PER NEC 210.62, YOU ARE REQUIRED TO HAVE AN
 OUTLET AT THE TOP OF EVERY SHOW WINDOW FOR EVERY 12' OR
 FRACTION THEREOF. THIS OUTLET SHALL BE WITHIN 18" OF
 THE TOP OF THE WINDOW.
 6.AS PER NEC 600.5, YOU ARE TO HAVE A DEDICATED SIGN
 OUTLET LOCATED ACCESSIBLE ABOVE EVERY ENTRANCE.
 7. AS PER NEC 700.12(F) EMERGENCY LIGHTING SHALL BE ON
 THE SAME LIGHTING CIRCUIT AS THE AREA THEY OCCUPY.
 INDICATE LIGHTING CIRCUIT NUMBER TO ASCERTAIN
 COMPLIANCE.
 8. AS PER FBC 2010 ENERGY 502.3.8, ALL RECESSED
 LIGHTING SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACE.
 9. AS PER FBC 2010 ENERGY, ALL LIGHTING SHALL COMPLY
 WITH SECTION 505.
  