2015-05-19 16:58:41 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15050177 |
| ADD: 1152 OKEECHOBEE RD |
| CONT: ABACOA CONSTRUCTION |
| TEL: (561)722-3890 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUESDAY MAY 19/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET LS-1 SHOWS A RAISED PLATFORM AND STAGE. SHEET |
| D-1 INDICATES A FLOOR LOADING OF 55 LBS. THIS OCCUPANCY |
| IS DECLARED AN A2 NIGHTCLUB. THE MINIMUM UNIFORM |
| DISTRIBUTED LOADS FOUND IN FBC-B TABLE 1607.1(4) 125 |
| PSF AND THE STAIRS 100 PSF. |
| |
| 2) SHEET LS-1 THE RAISED PLATFORM WILL NEED TO ALL THE |
| RISERS TO BE THE SAME HEIGHT AS REQUIRED IN 2010 FBC-B |
| 1009.4.2 RISER HEIGHT AND TREAD DEPTH. STAIR RISER |
| HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM AND 4 INCHES |
| (102 MM) MINIMUM. 1009.4.4 DIMENSIONAL UNIFORMITY. |
| STAIR TREADS AND RISERS SHALL BE OF UNIFORM SIZE AND |
| SHAPE. THE TOLERANCE BETWEEN THE LARGEST AND SMALLEST |
| RISER HEIGHT OR BETWEEN THE LARGEST AND SMALLEST TREAD |
| DEPTH SHALL NOT EXCEED 3/8 INCH (9.5 MM) IN ANY FLIGHT |
| OF STAIRS. |
| |
| 3) DISCREPANCY IN PLAN, THE PLANS INDICATE 3 RISERS, |
| FROM THE CITYS VISIT OF SITE AND PICTURES OF THE |
| LOCATION THE REISERS ARE NOT UNIFORM AND REVIEW THE |
| AMOUNT OF RISERS SHOWN IN PLAN (3) 3 X 7+ 21 INCHES, |
| THE PLANS INDICATE THE PLATFORM HEIGHT OF 14 INCHES. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED |
| DESCREPANCY IN PLANS. |
| |
| 4) THE PLATFORM DOES NOT SHOW HOW VERTICAL |
| ACCESSIBILITY WILL BE ACHIEVED, PLEASE PROVIDE |
| COMPLIANCE WITH THE 2010 FBC-ACCESSIBILITY CODE, |
| 201.1.1 VERTICAL ACCESSIBILITYSECTIONS 553.501-553.513, |
| F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO |
| NOT RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR |
| FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO |
| PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND |
| BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER |
| THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN |
| SUCH BUILDING, STRUCTURE OR FACILITY. |
| |
| 5) THE PLATFORM ALSO IS MISSING A HANDRAIL REQUIRED BY |
| FBC-ACCESSIBILITY CODE 504.6 HANDRAILS. STAIRS SHALL |
| HAVE HANDRAILS COMPLYING WITH 505. 505.2 WHERE |
| REQUIRED. HANDRAILS SHALL BE PROVIDED ON BOTH SIDES OF |
| STAIRS AND RAMPS. |
| |
| 505.4 HEIGHT. |
| TOP OF GRIPPING SURFACES OF HANDRAILS SHALL BE 34 |
| INCHES (865 MM) MINIMUM AND 38 INCHES (965 MM) MAXIMUM |
| VERTICALLY ABOVE WALKING SURFACES, STAIR NOSINGS, AND |
| RAMP SURFACES. HANDRAILS SHALL BE AT A CONSISTENT |
| HEIGHT ABOVE WALKING SURFACES, STAIR NOSINGS, AND RAMP |
| SURFACES. |
| |
| 505.10 HANDRAIL EXTENSIONS. |
| HANDRAIL GRIPPING SURFACES SHALL EXTEND BEYOND AND IN |
| THE SAME DIRECTION OF STAIR FLIGHTS AND RAMP RUNS IN |
| ACCORDANCE WITH 505.10. |
| |
| 6) THE DJ BOOTH DOES NOT INDICATE IF THIS IS ABOVE THE |
| FLOOR OR A PIT BENEATH THE FLOOR LEVEL. SHEET D1 DOES |
| NOT GIVE ANY ELEVATIONS NEITHER DOES SHEET LS1. |
| 107.2.1.3. |
| |
| 7) SHEET LS-1 INDICATES ON THE FLOOR PLAN A BAR AND |
| CONCESSION AREA WITH COUNTER, PLEASE PROVIDE COMPLIANCE |
| WITH THE 2010 FBC-ACCESSIBLITY CODE 904.4 SALES AND |
| SERVICE COUNTERS. |
| |
| 8) SHEET LS-1 PLEASE PROVIDE A DOOR SCHEDULE FOR ALL |
| DOORS, COMPLIANCE FOR FBC-B 1008.1.1 AND ACCESS. CODE |
| 404.2.3. |
| |
| SHEET LS-1 PLEASE PROVIDE DIMENSIONS FOR ALL RESTROOMS |
| AND SHOWER STALLS TO REVIEW FOR REQUIRED ACCESSIBLITY |
| ISSUES, PLEASE PROVIDE ENLARGED FLOOR PLAN & ELEVATION |
| OF BATHROOMS AND SHOWERS FOR ACCESSIBILITY. SHOW |
| CLEARANCES BETWEEN FIXTURES, GRAB BAR HEIGHTS, BACKING |
| FOR GRAB BARS ETC... CHAPTER 6 OF FL ACCESS. CODE. |
| |
| 9) SHEET LS-1THE PLANS FAIL TO PROVIDE SQ. FEET AREA OF |
| OCCUPANCIES AND ACCESSORY OCUPANCIES INDICATE THE |
| SQUARE FOOTAGE OF EACH AREA TO SEE IF THIS BUILDING |
| QUALIFIES AS A MIXED USE OCCUPANCY BETWEEN THE A2 AND |
| STORGE ROOM. SEE FBC-B TABLE 508.4 FOR HOUR RATINGS. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |