2015-11-13 12:02:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE SITE PLAN TO SHOW DISTANCE TO PROPERTY LINES
 AND TO OTHER STRUCTURES, FBC TABLE 602.
  
 ENGINEER'S RESPONSE LETTER STATES THAT THIS WAS
 ADDRESSED. I AM UNABLE TO LOCATE THE DIMENSION FROM THE
 PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE, THE
 BUILDING TO THE NORTH, OR THE PROPERTY LINE TO THE
 WEST. ALSO, IF THE DISTANCE TO THE EXISTING BUILDING IS
 LESS THAN 60', SHOW THE ASSUMED PROPERTY LINE AND
 DISTANCE FROM EACH STRUCTURE TO THE ASSUMED PROPERTY
 LINE, FBC 5TH EDITION 705.3.
  
 2. CONFLICTING INFORMATION PREVENTS PROVIDING AN
 ACCURATE REVIEW AT THIS TIME. OCCUPANCY IS F3, BUT NO
 INFORMATION PROVIDED REGARDING THE FACTORY OPERATIONS
 WHICH ARE TO TAKE PLACE IN THE PROPOSED STRUCTURE. THE
 RESPONSE LETTER FOR FIRE STATES THAT THIS WILL BE
 STORAGE.
  
 THE PLAN IS THE OFFICIAL PERMIT RECORD. PROVIDE MORE
 INFORMATION REGARDING THE FACTORY USE OF THE SPACE,
 MATERIALS TO BE USED, CHEMICALS TO BE STORED, ETC. ALSO
 PROVIDE A PLAN WHICH SHOWS COMPLIANCE WITH FBC
 ACCESSIBILITY OR INCORPORATE APPLICABLE EXCEPTIONS INTO
 THE PLAN.
  
 SEE DESCRIPTION OF F3 - "SHALL INCLUDE, AMONG OTHERS,
 THE OCCUPANCIES LISTED IN THIS SECTION: STEEL MILLS,
 PAPER PLANTS AND GENERATING PLANTS."
  
 3. NOT ENOUGH INFORMATION PROVIDED REGARDING THE DOOR:
  
 THE ELEVATION DIFFERENCE AT THE DOORS WAS NOT SHOWN. DO
 THE DOORS HAVE A THRESHOLD, OR IS IT A VERTICAL PIECE
 OF METAL AT THE BOTTOM? 1008.1.7
 REVISE PLAN TO SHOW COMPLIANCE WITH SEE FBC 1003.3,
 1003.5, 1008.1.3, 1008.1.1 (4' MAX DOOR WIDTH),
 1008.1.9.
 PROVIDE DOOR HEIGHT, 1008.
 PROVIDE HARDWARE INFORMATION - 1008.1.9. ALSO PROVIDE
 INFORMATION ON HOW DOES THE DOOR OPEN FROM THE INSIDE?
  
 ANY EXCEPTIONS USED ARE TO BE INCORPORATED INTO THE
 PLAN.
  
 4. REVISE PLAN TO INCLUDE OCCUPANT LOAD, FBC 1004.
  
 5. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  
  