Plan Review Notes For Permit 15050170 |
Permit Number |
15050170 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-07-07 10:26:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) BASED ON YOUR RESPONSE THAT THE TRAILER WILL BE | | INSTALLED FOR A PERIOD OF TWO YEARS IT IS CLASSIFIED AS | | A PERMANANT STRUCTURE PER NFPA 101, 3.3.271.9 AND | | 3.3.271.8. | | | | 2) THE STRUCTURE IS INDICATED AS A STORAGE OCCUPANCY. | | WILL THE STRUCTURE BE OCCUPIED AS AN OFFICE SPACE AND | | WHAT IS THE OCCUPANCY LOAD? | | | | 3) WHAT IS THE HAZARD CLASSIFICATION. WILL THE STORAGE | | OF FLAMMABLE LIQUID OR GASES, IE. GASOLINE, PROPANE, | | ACETYLENE, ETC. | | | | 4) A LIFE SAFETY PLAN WAS NOT ATTACHED. | | | | 5) EXIT SIGNS WERE NOT INDICATED. | | | | 6) EMERGENCY LIGHTING WAS NOT INDICATED. | | | | 7) THE SUBMITTED PLAN DOES NOT INDICATED ANY DOORS | | AND/OR DOOR SIZES, HARDWARE, ETC. | | | | 8) THE STROAGE HAZARD WAS NOT INDICATED. | | | | 9) FIRE EXTINGUSIHERS WERE NOT INDICATED. | | | | |
|