Plan Review Notes
Plan Review Notes For Permit 15050153
Permit Number 15050153
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-07 11:27:541) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING,
 FIXED, MOBILE, OR PORTABLE, SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3
 LISTING.
  
 2) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 4) PROVIDE PROOF OF OVERALL VALUE OF THE PROJECT IS
 REQUIRED AND SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ARCHITECTURAL DESIGN FEES, FABRICATION,
 STRUCTURAL, AND ELECTRICAL, PLUS OVERHEAD AND PROFIT.
 FINAL PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL. FBC WPB AMENDMENTS. SECTION 109.3
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]