2015-05-06 16:10:14 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- HOUSE VALUE IS MORE THAN $300,000. NEED TO COMPLY |
| WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC. |
| 611.8 OF 2010 FBC-EXISTING BUILDING. |
| |
| 2- HOUSE VALUE IS MORE THAN $750,000. NEED TO COMPLY |
| WITH THE OPENING PROTECTION FOR DOORS AND WINDOWS AS |
| REQUIRED BY SEC. 105.15 OF CITY AMENDMENTS TO FBC. |
| |
| 3- FLAT ROOF: THE DESIGN PRESSURES OF SELECTED ASSEMBLY |
| W51 DON'T MEET THE CORNER DESIGN PRESSURES FOR THIS |
| HOUSE AS REQUIRED BY SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. . THIS HOUSE IS LOCATED IN EXPOSURE |
| "D". NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS OR SELECT ANOTHER ASSEMBLY THAT MEET THE |
| DESIGN PRESSURES FOR EXPOSURE "D". |
| |
| 4- ROOFING UNDERLAYMENT FL11915-R4 SUBMITTED: |
| A) #30 FELT CAN NOT BE USED FOR FOAM-ON TILE |
| APPLICATIONS. SEE TABLE 1 ON PAGE 3 OF 8. |
| |
| B) SELF-ADHERING UNDERLAYMENTS CAN NOT BE USED EITHER. |
| THE MAXIMUM DESIGN PRESSURES FOR SELF ADHERING |
| UNDERLAYMENT IS -45PSF. SEE SEC. 5.6.3 ON PAGE 4 OF 8. |
| THESE DESIGN PRESSURES DON'T MEET THE DESIGN PRESSURES |
| REQUIRED BY SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |