Plan Review Notes
Plan Review Notes For Permit 15050120
Permit Number 15050120
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-11 11:25:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
 PROFLEX SIM-90 SPECS & TEST REPORTS PROVIDED
  
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED INCLUDES A SUSPENDED GYPSUM
 CEILING. SINCE THE UNIT BELOW DOES NOT HAVE A SUSPENDED
 GYPSUM CEILING, PROVIDE A COPY OF A TEST REPORT WHICH
 DOES NOT INCLUDE A SUSPENDED CEILING.
 THE TEST WAS DONE ON AN 8" SLAB. PROVIDE SLAB
 THICKNESS.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED INCLUDES A SUSPENDED GYPSUM
 CEILING. SINCE THE UNIT BELOW DOES NOT HAVE A SUSPENDED
 GYPSUM CEILING, PROVIDE A COPY OF A TEST REPORT WHICH
 DOES NOT INCLUDE A SUSPENDED CEILING.
 THE TEST WAS DONE ON AN 8" SLAB. PROVIDE SLAB
 THICKNESS.
  
 3. ONLY ONE SET OF THE SOUND TESTS WAS PROVIDED. TWO
 COMPLETE COLLATED SETS OF DOCUMENTS REQUIRED FOR PERMIT
 ISSUANCE. FAILURE TO PROVIDE TWO COMPLETE SETS MAY
 RESULT IN ADMINISTRATIVE FEES, FBC 107.
  
  