Plan Review Notes
Plan Review Notes For Permit 15050111
Permit Number 15050111
Review Stop G
Sequence Number 1
Notes
Date Text
2015-05-07 06:15:001) PROVIDE SPEC SHEETS FOR THE EXTERIOR REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER 2010
 FBC-R SEC.G2421.1.
 2) SHOW THE LENGTHS OF ALL SECTIONS OF PIPE FROM THE
 LINE EXITING THE METER TO THE POOL HEATER. THE PLANS
 SHOW THE DIMENSIONS OF ONLY 2 SECTIONS OF PIPE THAT
 TOTAL 25 FEET BUT THE PLAN STATES THE DEVELOPED LENGTH
 IS 20 FEET. IT DOES NOT ADD UP.WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 3) INDICATE ON THE PLAN HOW THE GALVANIZED PIPE TO THE
 POOL HEATER IS GOING TO BE INSTALLED. GALVANIZED PIPE
 CANNOT BE INSTALLED UNDERGROUND PER 2010 FBC-R
 SEC.G2415.9, G2415.9.2. IF THE PIPING IS TO BE ATTACHED
 TO THE EXTERIOR OF THE WALL, INDICATE SO ON PLANS. WPB
 AMEND. TO 2010 FBC SEC.107.2.1..
 4) SHOW THE HOT AND COLD WATER LINES ON THE PLAN.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 5) THE PLAN NOTES THE GAS METER AS 1/2 POUND SYSTEM AND
 ALSO A 2 LB. SYSTEM. WHICH IS IT? IF IT IS A HALF POUND
 SYSTEM, THE SYSTEM IS UNDERSIZED FOR THE BTU LOAD.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  