Plan Review Notes
Plan Review Notes For Permit 15050093
Permit Number 15050093
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-18 17:25:00APPROVED W/PROVISOS AS MENTIONED BELOW:
  
 1. IF ITEM #7 ON RISER DIAGRAM RUNS UNDERGROUND
 CONDUCTOR INSULATION SHALL BE THWN TYPE
 2. OUTLETS MARKED ON PLANS SHALL BE INSTALLED
 3. CARBON MONOXIDE DETECTORS REQUIRED
 4. ARC-FAULT CIRCUIT PROTECTION REQUIRED
 5. TAMPER-RESISTANT DEVICES REQUIRED
 6. CEILING BOXES TO BE LISTED FOR 50#?S
  
 ALL WORK IS SUBJECT TO FIELD INSPECTOR?S APPROVAL
  