Notes |
Date |
Text |
2015-05-16 09:21:40 | 1) THE SINK IN MOH'S LAB RM.# 115 IS NOT SHOWN ON THE | | SANITARY RISER.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | 2) SHT. A-1 - THE GRAB BAR'S HEIGHT SHALL BE MEASURED | | TO THE TOP OF THE GRIPPING SURFACE. 2010 | | FBC-ACCESSIBILITY, SEC.609.4. | | 3) IDENTIFY THE DRINKING FOUNTAIN ON THE WATER AND | | SANITARY RISERS. | | 4) SHOW THE TERMINATION POINT OF THE CONDENSATE DRAIN | | FROM THE A/C UNIT.CONDENSATE SHALL NOT DISCHARGE TO THE | | CITY'S SANITARY SYSTEM PER CITY ORDINANCE. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|