Plan Review Notes
Plan Review Notes For Permit 15050067
Permit Number 15050067
Review Stop P
Sequence Number 1
Notes
Date Text
2015-05-16 09:21:401) THE SINK IN MOH'S LAB RM.# 115 IS NOT SHOWN ON THE
 SANITARY RISER.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. A-1 - THE GRAB BAR'S HEIGHT SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. 2010
 FBC-ACCESSIBILITY, SEC.609.4.
 3) IDENTIFY THE DRINKING FOUNTAIN ON THE WATER AND
 SANITARY RISERS.
 4) SHOW THE TERMINATION POINT OF THE CONDENSATE DRAIN
 FROM THE A/C UNIT.CONDENSATE SHALL NOT DISCHARGE TO THE
 CITY'S SANITARY SYSTEM PER CITY ORDINANCE.
  
 PLUMBING PLAN REVIEW