Plan Review Notes For Permit 15050067 |
Permit Number |
15050067 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-14 14:17:18 | REVIEWED BY CHRIS COLE | | | | 1) SHEET M-2: A DUCT SMOKE DETECTOR IS REQUIRED PER | | SECTION 606.2.1 FMC-10. SHOW THE LOCATION OF THE DEVICE | | AND TEST STATION PER SECTION 606.4.1 FMC-2010. | | 2) PROVIDE WIND LOAD ENGINEERED TIE-DOWN DETAILS FOR | | INSTALLATION OF THE CU ON THE EXISTING STAND- SECTION | | 301.12 FMC-10. SUBMIT TWO COPIES OF VALID FL. PRODUCT | | APPROVALS OR MIAMI-DADE NOA'S FOR THE INTAKE AND | | EXHAUST LOUVERS. | | 3) VERIFY THE AIR INTAKE WILL HAVE A MINIMUM 10' | | HORIZONTAL CLEARANCE TO THE STREET OR PARKING LOT- | | SECTION 401.4.1 FMC-10. | | 4) AN AIR INTAKE DAMPER THAT WILL AUTIOMATICALLY SHUT | | IS REQUIRED PER SECTION 503.2.5.4 FBC-10 ENERGY | | CONSERVATION. SHOW THE LOCATION ON SHEET M-2, AND | | CORRECT THE NOTES ON THE AHU DETAIL ON SHEET M-1. | | 5) PLEASE NOTE THAT THE CONDENSATE FROM THE AIR HANDLER | | IS NOT PERMITTED TO DRAIN INTO THE CITY SANITARY SYSTEM | | PER SECTION 90-203 WPB CODE OR ORDINANCES. | | INDICATE ON THE PLAN THE ACTUAL DRAINAGE LOCATION. | | | | CHRISTOPHER COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|