Notes
Date Text
2015-05-14 14:17:18REVIEWED BY CHRIS COLE
  
 1) SHEET M-2: A DUCT SMOKE DETECTOR IS REQUIRED PER
 SECTION 606.2.1 FMC-10. SHOW THE LOCATION OF THE DEVICE
 AND TEST STATION PER SECTION 606.4.1 FMC-2010.
 2) PROVIDE WIND LOAD ENGINEERED TIE-DOWN DETAILS FOR
 INSTALLATION OF THE CU ON THE EXISTING STAND- SECTION
 301.12 FMC-10. SUBMIT TWO COPIES OF VALID FL. PRODUCT
 APPROVALS OR MIAMI-DADE NOA'S FOR THE INTAKE AND
 EXHAUST LOUVERS.
 3) VERIFY THE AIR INTAKE WILL HAVE A MINIMUM 10'
 HORIZONTAL CLEARANCE TO THE STREET OR PARKING LOT-
 SECTION 401.4.1 FMC-10.
 4) AN AIR INTAKE DAMPER THAT WILL AUTIOMATICALLY SHUT
 IS REQUIRED PER SECTION 503.2.5.4 FBC-10 ENERGY
 CONSERVATION. SHOW THE LOCATION ON SHEET M-2, AND
 CORRECT THE NOTES ON THE AHU DETAIL ON SHEET M-1.
 5) PLEASE NOTE THAT THE CONDENSATE FROM THE AIR HANDLER
 IS NOT PERMITTED TO DRAIN INTO THE CITY SANITARY SYSTEM
 PER SECTION 90-203 WPB CODE OR ORDINANCES.
 INDICATE ON THE PLAN THE ACTUAL DRAINAGE LOCATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  