Plan Review Notes For Permit 15050053 |
Permit Number |
15050053 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-13 15:50:23 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) AT LEAT ONE GFI RECEPTACLE OUTLET SHALL BE INSTALL | | ON A PORCH OR BALCONY ACCESSIBLE FROM INSIDE. NEC | | 210.52(E))(3) AND NEC 210.8 | | | | 2) TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS. IN | | ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15- AND | | 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPERRESISTANT | | RECEPTACLES. NEC 406.11 | | | | 3) RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE | | AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE | | ATTACHMENT PLUG CAP IS INSERTED. ALL 15- AND 20-AMPERE, | | 125- AND 250-VOLT NONLOCKING RECEPTACLES SHALL BE | | LISTED WEATHER-RESISTANT TYPE. NEC 406.8 (B) (1) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|