Plan Review Notes For Permit 15050014 |
Permit Number |
15050014 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-08 07:10:52 | 1) SHT. C-2 SHALL BE SIGNED AND SEALED BY THE ENGINEER | | WHOSE NAME APPEARS ON THE DRAWING. F.A.C. RULE | | 61G15-23.002. | | 2) INDICATE THE BTU LOAD OF THE GENERATOR ON THE | | DRAWING. HOW CAN PIPE SIZE BE CONFIRMED AS CODE | | COMPLIANT WITHOUT KNOWING THE BTU LOAD OF THE | | EQUIPMENT? | | 3 )SHOW THE DISTANCE OF THE RELIEF VALVE DISCHARGE ON | | THE TANK FROM THE UTILITY RACK. IS THIS A POSSIBLE | | SOURCE OF IGNITION? IF SO, A DISTANCE OF 10 FT. SHALL | | BE MAINTAINED. | | 4) THE TANK IS LOCATED NEAR A VEHICLE GATE. PROTECTION | | SHALL BE PROVIDED FOR THE TANK FITTING HOUSING,HOUSING | | COVER, TANK CONNECTIONS AND PIPNG WHERE CONTAINERS ARE | | INSTALLED WITHIN 10 FT. OF WHERE VEHICULES CAN BE | | EXPECTED PER NFPA 58, SEC. 6.6.6 (D). | | 5) SHOW THE DISTANCE OF THE TANK FROM THE EQUIPMENT | | SHELTER. COMPL W/ NFPA 58 SEC.6.3.4.2. MEASUREMENTS | | SHALL BE FROM THE PRESSURE RELIEF VALVE AND THE FILLING | | CONNECTION OF THE TANK. NFPA 58, SEC.6.3.4.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|