Plan Review Notes
Plan Review Notes For Permit 15050014
Permit Number 15050014
Review Stop G
Sequence Number 1
Notes
Date Text
2015-05-08 07:10:521) SHT. C-2 SHALL BE SIGNED AND SEALED BY THE ENGINEER
 WHOSE NAME APPEARS ON THE DRAWING. F.A.C. RULE
 61G15-23.002.
 2) INDICATE THE BTU LOAD OF THE GENERATOR ON THE
 DRAWING. HOW CAN PIPE SIZE BE CONFIRMED AS CODE
 COMPLIANT WITHOUT KNOWING THE BTU LOAD OF THE
 EQUIPMENT?
 3 )SHOW THE DISTANCE OF THE RELIEF VALVE DISCHARGE ON
 THE TANK FROM THE UTILITY RACK. IS THIS A POSSIBLE
 SOURCE OF IGNITION? IF SO, A DISTANCE OF 10 FT. SHALL
 BE MAINTAINED.
 4) THE TANK IS LOCATED NEAR A VEHICLE GATE. PROTECTION
 SHALL BE PROVIDED FOR THE TANK FITTING HOUSING,HOUSING
 COVER, TANK CONNECTIONS AND PIPNG WHERE CONTAINERS ARE
 INSTALLED WITHIN 10 FT. OF WHERE VEHICULES CAN BE
 EXPECTED PER NFPA 58, SEC. 6.6.6 (D).
 5) SHOW THE DISTANCE OF THE TANK FROM THE EQUIPMENT
 SHELTER. COMPL W/ NFPA 58 SEC.6.3.4.2. MEASUREMENTS
 SHALL BE FROM THE PRESSURE RELIEF VALVE AND THE FILLING
 CONNECTION OF THE TANK. NFPA 58, SEC.6.3.4.1.
  