Plan Review Notes
Plan Review Notes For Permit 15050012
Permit Number 15050012
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-04 15:33:46REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INDICATE THE LOCATION IN COMPLIANCE WITH THE NEC
 230.70
  
 2) INDICATE THE SIZE (AMPACITY RATING) OF THE MAIN
 OCPD, NEC 230.42 MINIMUM SIZE AND RATING.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  