Plan Review Notes For Permit 15041163 |
Permit Number |
15041163 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-06-12 06:52:29 | ****CORRECTIONS**** | | ****COURTESTY REVIEW VIA EMAIL**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | IIC TEST FOR QUIETWALK UNDERLAYMENT WITH LAMINATE | | FLOORING WAS SENT VIA EMAIL | | | | 1. FBC 2010 1207.2, 1207.3: | | | | A. THE IIC TEST PROVIDED IS ACCEPTABLE. | | | | B. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, | | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED | | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE | | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL | | NOT BE ALTERED. | | | | PLEASE PROVIDE A COPY OF THE TEST REPORT. | | | | 2. FROM PREVIOUS LIST: | | | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | E 84 OR UL 723. | | | | NOT PROVIDED. | | |
|