Plan Review Notes For Permit 15041163 |
Permit Number |
15041163 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-06-06 19:10:42 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | | | | | 1. FBC 2010 1207.2, 1207.3: | | | | FLOORING UNDERLAYMENT TESTS PROVIDED WERE FOR | | WHISPERMAT HW, 8" SLAB, 7/16" HARDWOOD T&G FLOORING | | | | FOR THE FLOORING UNDERLAYMENT, COMPLIANCE IS NOT CLEAR. | | PROVIDE INFORMATION REGARDING THE SLAB THICKNESS FOR | | THIS BUILDING. | | | | EITHER PROVIDE TEST REPORTS WHICH ARE CONSISTENT WITH | | THE PROPOSED INSTALLATION (LAMINATE FLOORING, THICKNESS | | NOT PROVIDED) OR PROVIDE OTHER DATA FROM THE | | MANUFACTURER FOR CONSIDERATION. | | | | THIS INFORMATION MAY BE SENT VIA EMAIL FOR PRELIMINARY | | REVIEW. | | | | 2. FROM PREVIOUS LIST: | | | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | E 84 OR UL 723. | | | | | | |
|