Plan Review Notes
Plan Review Notes For Permit 15041163
Permit Number 15041163
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-03 09:49:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, SCOPE NOT CLEAR. FLOORING UNDERLAYMENT SPEC
 SHEET PROVIDED, BUT PLANS DO NOT INDICATE FLOORING
 INSTALLATION. THE PLAN IS TO BE ARCHITECTURAL QUALITY,
 TO SCALE, AND TO CLEARLY SHOW SCOPE AND NATURE OF
 PROPOSED IMPROVEMENT.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED UTILIZED A SUSPENDED GYPSUM
 CEILING. EITHER PROVIDE EVIDENCE THAT THE UNIT BELOW
 INCLUDES A SUSPENDED GYPSUM CEILING WHICH WILL NEVER BE
 REMOVED, OR PROVIDE A TEST REPORT WHICH DOES NOT
 INCLUDE THE SUSPENDED GYPSUM CEILING.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED UTILIZED A SUSPENDED GYPSUM
 CEILING. EITHER PROVIDE EVIDENCE THAT THE UNIT BELOW
 INCLUDES A SUSPENDED GYPSUM CEILING WHICH WILL NEVER BE
 REMOVED, OR PROVIDE A TEST REPORT WHICH DOES NOT
 INCLUDE THE SUSPENDED GYPSUM CEILING.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  