2015-05-02 10:28:39BUILDING PLAN REVIEW
 SUBMITTAL : 15041155
 PERMIT: 14080059
 ADD: 5660 N MILITARY TRL.
 CONT: SISCA
 TEL: (561)228-7503
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. MAY 02/ 2015
 ACTION: DENIED BUILDING PROVISO
  
 NOTE/ PROVISO: DEFERRED SUBMITTALS: FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOOR/ STOREFRONT
 (B) WINDOWS/ STOREFRONT
 (D) ROOFING PRODUCTS AND ASSEMBLIES , 3 FT. PARAPET,
 MAY REQUIRE ENHANCED FASTENING IN ROOF ZONES 2 -63.8
 PSF @ 15 FT. (NO ZONE 3 / 3 FT PARAPET).
  
 1) THE PRODUCT APPROVALS HAVE NOT BEEN SUBMITED TO
 DATE.
 (2) COPIES OF SHOP DRAWINGS FOR US ALUMINUM IG500
 SUBMITTED BUT NO PRODUCT APPROVAL
 (1) COPY OF SHOP DRAWINGS STORE FRONT US ALULINUM
 IG500/ IG600 SERIE, NO PRODUCT APPROVALS
  
 2) ROOFING APPROVALS SUBMITTED:
 BILCO ROOF HATCH NOA:14-0708.07 10 SHEETS SUBMITTED 3.
  
 ROOFING: FL9930-R6 JOHN MANVILLE SINGLE PLY APPENDIX
 SHEET 1 SUB-SYSTEM 2C-1 HIGHLIGHTED, SHEET 10
 SUB-SYSTEM S-38 MAXIMUM DESIGN PRESSURE -45.0.
 SEE PROVISO ABOVE THE REQUIRED PRESSURES IN ZONE # 2
 REQUIRE -63.8.SEE PAGE 2 OF REPORT NOTE # 9 FOR
 MECHANICALLY ATTACHED COMPONENTS. REQUIRES
 CALCULATIONS FROM AN ARCHITECT OR ENGINEER.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved