Plan Review Notes
Plan Review Notes For Permit 15041144
Permit Number 15041144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-05-04 14:13:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 SHEET FP - 1: THERE IS INCORRECT REFERNECE TO THE FIRE
 CODE. ALL INSTALLATIONS SHALL COMPLY WITH THE
 REQUIRERMENTS OF NFPA 13, 2010 EDITION
  
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL
 NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
  