Plan Review Notes
Plan Review Notes For Permit 15041142
Permit Number 15041142
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-16 13:33:385/16/2015
 PROJECT: LOFTIN PLACE TEMP. LEASING OFFICE.
 PERMIT#: 15041142
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED.
  
 PLEASE CLARIFY THE FOLLOWING ELECTRICAL REVIEW
 COMMENTS.
  
 1) THE SERVICE DIAGRAM INDICATED ON THE EAST ELEVATION
 ON SHEET A-2 IS DIAGRAMATICALLY DIFFERENT THAN THE
 RISER DIAGRAM INDICATED ON SHEET E-1 AND YET AGAIN ON
 THE FIRST FLOOR PLAN THERE APPEARS TO BE TWO ELECTRICAL
 SERVICES. NEC 230.2 NUMBER OF SERVICES.
  
 2) THE NOTE ON SHEET E.2 THAT CALLS FOR THE DEMOLITION
 OF THE KITCHEN. PLEASE PROVIDE A DEMOLITION DETAIL THAT
 NOTES THE EXTENT OF THE DEMOLITION AND A NEW PLAN THAT
 INDICATES THE PROPOSED FINISHED KITCHEN.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SECURITY, CCTV, AUDIO/VIDEO, NETWORK,
 DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  