2015-05-16 13:33:38 | 5/16/2015 |
| PROJECT: LOFTIN PLACE TEMP. LEASING OFFICE. |
| PERMIT#: 15041142 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED. |
| |
| PLEASE CLARIFY THE FOLLOWING ELECTRICAL REVIEW |
| COMMENTS. |
| |
| 1) THE SERVICE DIAGRAM INDICATED ON THE EAST ELEVATION |
| ON SHEET A-2 IS DIAGRAMATICALLY DIFFERENT THAN THE |
| RISER DIAGRAM INDICATED ON SHEET E-1 AND YET AGAIN ON |
| THE FIRST FLOOR PLAN THERE APPEARS TO BE TWO ELECTRICAL |
| SERVICES. NEC 230.2 NUMBER OF SERVICES. |
| |
| 2) THE NOTE ON SHEET E.2 THAT CALLS FOR THE DEMOLITION |
| OF THE KITCHEN. PLEASE PROVIDE A DEMOLITION DETAIL THAT |
| NOTES THE EXTENT OF THE DEMOLITION AND A NEW PLAN THAT |
| INDICATES THE PROPOSED FINISHED KITCHEN. |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SECURITY, CCTV, AUDIO/VIDEO, NETWORK, |
| DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |