2015-06-03 09:27:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA,
 FBC1603.1.4 (WIND SPEED, EXPOSURE CLASSIFICATION).
  
 2. REVISE PLAN TO INCLUDE ASCE 24 FOR DESIGN CRITERIA,
 FBC 1612.4. AS THIS IS A STRUCTURE, NOT A BUILDING, AN
 ELEVATION CERTIFICATE IS NOT REQUIRED BUT DESIGN FOR
 RESISTANCE TO FLOOD LOADS IS REQUIRED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED PLANS READY
 FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE RETAINED IN
 THE PERMIT APPLICATION PACKAGE (SEPARATE FROM THE
 PERMIT SETS) AND MARKED *OLD SHEETS* OR *VOID*. PLEASE
 KEEP BOTH SETS OF OLD VOIDED SHEETS IN THE PERMIT
 PACKAGE.
  