| PROJECT: RELIEF AUTO BODY |
| PERMIT#: 15041121 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) NEC 220. |
| PROVIDE A TOTAL CONNECTED LOAD SUMMARY CALCULATION |
| INDICATING THE ADDITIONAL LOAD OF THE NEW SPRAY BOOTH |
| EQUIPMENT. |
| |
| 2) NEC 230.42(B) |
| THE SERVICE ENTRANCE INDICATED ON THE RISER DIAGRAM HAS |
| BEEN UNDERSIZED. THE MINIMUM AMPACITY FOR UNGROUNDED |
| CONDUCTORS FOR SPECIFIC INSTALLATIONS SHALL NOT BE LESS |
| THAN THE RATING OF THE SERVICE DISCONNECTING MEANS. |
| |
| 3) NEC 310.16 |
| USE THE NEC 310.16 TO SIZE THE SERVICE ENTRANCE |
| CONDUCTORS. |
| |
| 4) NEC 210.19(A) |
| THERE ARE CIRCUITS IN THE PANEL SCHEDULE WITH |
| UNDERSIZED CONDUCTORS CONNECTED TO OCPD. BRANCH-CIRCUIT |
| CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN THE |
| MAXIMUM LOAD TO BE SERVED. NEC 210.19(A) |
| |
| 5) NEC 408.4 |
| EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. NEC 408.4 |
| |
| 6) WPB AMENDMENTS TO THE FBC 107.2.5 |
| INDICATE THE LOCATION OF THE ELECTRICAL SERVICE ON THE |
| BUILDING RELATIVE TO THE LOCATION OF THE NEW SPRAY |
| BOOTH. |
| |
| 7) WPB AMENDMENTS TO THE FBC 107.2.5 |
| INDICATE THE LOACTION OF THE ELECTRICAL PANEL ON OR IN |
| THE BUILING RELATIVE TO THE LOCATION OF THE NEW SPRAY |
| BOOTH. |
| |
| 8) WPB AMENDMENTS TO THE FBC 107.3.5.1.2 |
| INDICATE THE LOCATION ON A FLOOR PLAN OF THE SWITCHES, |
| OUTLETS, LIGHTS, FANS, MOTORS, CONTROLERS, DISCONNECTS, |
| ETC ON, IN, ON, AND/OR AROUND THE SPRAY BOOTH. INDICATE |
| WHICH ARE NEW AND WHICH ARE EXISTING TO REMAIN. |
| |
| 9) NEC 516.3 |
| INDICATE THE HAZARDOUS LOCATIONS ON THE FLOOR PLAN AND |
| INDICATE WHICH OF THE DEVICES WITHIN THOSE LOCATIONS |
| ARE TO BE HOUSED AND OR PROTECTED BY EQUIPMENT SUITABLE |
| FOR THAT ENVIRONMENT. |
| |
| 10) NEC 516 |
| PROVIDE MANUFACTURER PRODUCT APPROVAL DOCUMENTS |
| INDICATING COMPLIANCE WITH THE NEC 110(3)(B) AND NEC |
| 516. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |