Plan Review Notes
Plan Review Notes For Permit 15041121
Permit Number 15041121
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-01 10:03:325/1/2015
 PROJECT: RELIEF AUTO BODY
 PERMIT#: 15041121
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) NEC 220.
 PROVIDE A TOTAL CONNECTED LOAD SUMMARY CALCULATION
 INDICATING THE ADDITIONAL LOAD OF THE NEW SPRAY BOOTH
 EQUIPMENT.
  
 2) NEC 230.42(B)
 THE SERVICE ENTRANCE INDICATED ON THE RISER DIAGRAM HAS
 BEEN UNDERSIZED. THE MINIMUM AMPACITY FOR UNGROUNDED
 CONDUCTORS FOR SPECIFIC INSTALLATIONS SHALL NOT BE LESS
 THAN THE RATING OF THE SERVICE DISCONNECTING MEANS.
  
 3) NEC 310.16
 USE THE NEC 310.16 TO SIZE THE SERVICE ENTRANCE
 CONDUCTORS.
  
 4) NEC 210.19(A)
 THERE ARE CIRCUITS IN THE PANEL SCHEDULE WITH
 UNDERSIZED CONDUCTORS CONNECTED TO OCPD. BRANCH-CIRCUIT
 CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN THE
 MAXIMUM LOAD TO BE SERVED. NEC 210.19(A)
  
 5) NEC 408.4
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 6) WPB AMENDMENTS TO THE FBC 107.2.5
 INDICATE THE LOCATION OF THE ELECTRICAL SERVICE ON THE
 BUILDING RELATIVE TO THE LOCATION OF THE NEW SPRAY
 BOOTH.
  
 7) WPB AMENDMENTS TO THE FBC 107.2.5
 INDICATE THE LOACTION OF THE ELECTRICAL PANEL ON OR IN
 THE BUILING RELATIVE TO THE LOCATION OF THE NEW SPRAY
 BOOTH.
  
 8) WPB AMENDMENTS TO THE FBC 107.3.5.1.2
 INDICATE THE LOCATION ON A FLOOR PLAN OF THE SWITCHES,
 OUTLETS, LIGHTS, FANS, MOTORS, CONTROLERS, DISCONNECTS,
 ETC ON, IN, ON, AND/OR AROUND THE SPRAY BOOTH. INDICATE
 WHICH ARE NEW AND WHICH ARE EXISTING TO REMAIN.
  
 9) NEC 516.3
 INDICATE THE HAZARDOUS LOCATIONS ON THE FLOOR PLAN AND
 INDICATE WHICH OF THE DEVICES WITHIN THOSE LOCATIONS
 ARE TO BE HOUSED AND OR PROTECTED BY EQUIPMENT SUITABLE
 FOR THAT ENVIRONMENT.
  
 10) NEC 516
 PROVIDE MANUFACTURER PRODUCT APPROVAL DOCUMENTS
 INDICATING COMPLIANCE WITH THE NEC 110(3)(B) AND NEC
 516.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  