Plan Review Notes
Plan Review Notes For Permit 15041121
Permit Number 15041121
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-19 14:03:06 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041121
 ADD: 1616 N FLORIDA MANGO
 CONT: MARYJULI
 TEL: ( 561)386-6032
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 416.7 SPRAY ROOMS SHALL BE SEPARATED BY 1 HOUR
 SEPARATION FIRE BARRIERS.
  
 2) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 416.7 SPRAY ROOMS. FLOORS SHALL BE WATER-PROOFED AND
 DRAINED IN AN APPROVED MANNER.
  
 3) SHOW COMPLIANCE WITH FBC-B 416.3 SPRAYING SURFACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FBC-MECHANICAL CODE.
  
 4) SHOW COMPLIANCE WITH 416.4 SPRAY BOOTHS SHALL BE
 DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE THE
 FLORIDA FIRE PREVENTION CODE. NFPA 33.
  
 5) THE PLANS NEED TO SHOW COMPLIANCE WITH: FBC-B 416.5.
 A AUTOMATIC FIRE EXTINGUISHING SYSTEM.
  
 6) THE PLANS WILL NEED TO SHOW COMPLIANCE WITH HOW THE
 ROOFTOP VENTS WILL BE ATTACHED/ ANCHORED TO RESIST THE
 MOMENT OF OVERTURNING IN A 170 VULT MPH/ 3 SECOND GUST
 WIND. THE ROOFTOP EXHAUST IS CONSIDERED COMPONENTS AND
 CLADDING.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  