Plan Review Notes
Plan Review Notes For Permit 15041085
Permit Number 15041085
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-09 09:04:39APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 600.3 LISTING. ELECTRIC SIGNS, SECTION SIGNS,
 AND OUTLINE LIGHTING SHALL BE LISTED AND INSTALLED IN
 CONFORMANCE WITH THAT LISTING..
  
 2) NEC 600.6(A)(1) EACH SIGN OR BRANCH CIRCUIT
 SUPPLYING A SIGN, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN.
  
 3) FBC-E 505.2.4. LIGHTING FOR ALL EXTERIOR
 APPLICATIONS NOT EXEMPTED IN SECTION 505.1 SHALL HAVE
 AUTOMATIC CONTROLS CAPABLE OF TURNING OFF EXTERIOR
 LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN
 THE LIGHTING IS NOT REQUIRED. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOCELL. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,