Plan Review Notes For Permit 15041085 |
Permit Number |
15041085 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-09 09:04:39 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) NEC 600.3 LISTING. ELECTRIC SIGNS, SECTION SIGNS, | | AND OUTLINE LIGHTING SHALL BE LISTED AND INSTALLED IN | | CONFORMANCE WITH THAT LISTING.. | | | | 2) NEC 600.6(A)(1) EACH SIGN OR BRANCH CIRCUIT | | SUPPLYING A SIGN, SHALL BE CONTROLLED BY AN EXTERNALLY | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN. | | | | 3) FBC-E 505.2.4. LIGHTING FOR ALL EXTERIOR | | APPLICATIONS NOT EXEMPTED IN SECTION 505.1 SHALL HAVE | | AUTOMATIC CONTROLS CAPABLE OF TURNING OFF EXTERIOR | | LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN | | THE LIGHTING IS NOT REQUIRED. LIGHTING DESIGNATED FOR | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN | | ASTRONOMICAL TIME SWITCH OR PHOTOCELL. ALL TIME | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING | | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|