Plan Review Notes
Plan Review Notes For Permit 15041067
Permit Number 15041067
Review Stop B
Sequence Number 2
Notes
Date Text
2015-05-27 09:04:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041067
 ADD: 529 S. FLAGLER DR. SUITE # 28-H
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)784-3722
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MAY 27/2015
 ACTION: DENIED
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION.
  
 1) 2ND REQUEST. DESIGN FOR WIND BY RAYOMND CHLADNY
 ARCHITECT, NOTE THE DESIGNER OF RECORD SEALED THE PLANS
 WITH HIS AA CERTIFICATE OF AUTHORITY SEAL. 61 G
 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000 THE
 PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT OR
 INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD
 AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS
 CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT.
 DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE
 RESPONSIBLE ARCHITECT
  
 2) 2ND REQUEST. NOTICE!!!!!!!!!!! PLEASE NOTE THE WIND
 DESIGN CRITERIA WAS PROVIDED, WHAT WAS NOT PROVIDED WAS
 THE SIZE OF THE WINDOWS AND DOORS NOR WHERE ZONE 4 AND
 5 START AND END. THE PRESSUES NEED TO ALIGN WITH THE
 SIZE OF OPENING AND ZONE EITHER 4 OR 5. EITHER THE
 ARCHITECT OR CONTRACTOR IS TO PROVIDE THE SIZES OF THE
 OPENINGS, TYPE OF GLAZING, SILL HEIGHT OF THE SLIDING
 DOORS TO BE INSTALLED, CIRCLE TO IDENTIFY AND
 ASSOCIATED PRESSURES. ON THE SUBMITTED PLANS THE
 ARCHITECT HAS STATED THAT THE MOST SEVERVE WIND
 PRESSURE COMES TO -98.45 PSF PLEASE PROVIDE THE SIZE OF
 THIS OPENING, IT APPEARS TO BE LOW.
  
 3) 2ND REQUEST . 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2ND REQUEST. SUBMITTED SUPERSAM 125 HAS A IIC RATING
 OF 49. PLEASE PROVIDE TESTING FOR CODE COMPLIANCE FOR
 FLOOR INSULATION: BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION
  
 4A) THE DESIGNER OF RECORD TO VERIFY THE SLAB THICKNESS
 FOR THIS BUILDING. THE SUBMITTED TESTING REPORT ASTM
 E-492 FOR PROFLEX MSC 90 WITH A IMPACT INSULATION CLASS
 IIC OF 68 DB IS WITH A SUSPENDED CEILING OF 5/8 INCH
 TYPE X DRYWALL ATTACHED TO A SUSPENDED RIGID X CEILING
 FRAME AND 3 1/2INCHES OF INSULATION. THE TEST HAS TO BE
 WITH THE TILE, THIN SET, SOUND UNDERLAYMENT AND
 ADHESIVE AND CONCRETE SLAB.
  
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 4B) THE SUBMITTED TESTING REPORT ASTM E-90 FOR PROFLEX
 MSC 90 WITH ASOUND TRANSMISSION CLASS OF STC= 72 DB FOR
 PROFLEX MSC 90 IS WITH A SUSPENDED CEILING OF 5/8 INCH
 TYPE X DRYWALL ATTACHED TO A SUSPENDED RIGID X CEILING
 FRAME AND 3 1/2INCHES OF INSULATION. THE TEST HAS TO BE
 WITH THE TILE, THIN SET, SOUND UNDERLAYMENT AND
 ADHESIVE AND CONCRETE SLAB.
  
 FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) COMPLIED. FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved