Plan Review Notes For Permit 15041067
Permit Number 15041067
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-04 16:15:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041067
 ADD: 529 S. FLAGLER DR. SUITE # 28-H
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)784-3722
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MAY 04/2015
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1) DESIGN FOR WIND BY RAYOMND CHLADNY ARCHITECT, NOTE
 THE DESIGNER OF RECORD SEALED THE PLANS WITH HIS AA
 CERTIFICATE OF AUTHORITY SEAL. 61 G 1-16.003 USES OF
 SEAL. EFFECTIVE 04/18/2000 THE PERSONAL SEAL, SIGNATURE
 AND DATE OF THE ARCHITECT OR INTERIOR DESIGNER SHALL
 APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND SHALL BE
 CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS CORPORATION.
 A CORPORATE SEAL ALONE IS INSUFFICIENT. DOCUMENTS SHALL
 BE SIGNED PERSONALLY AND SEALED BY THE RESPONSIBLE
 ARCHITECT
  
 2) PLEASE NOTE THE WIND DESIGGN CRITERIA WAS PROVIDED,
 WHAT WAS NOT PROVIDED WAS THE SIZE OF THE WINDOWS AND
 DOORS NOR WHERE ZONE 4 AND 5 START AND END.
 THE PRESSUES NEED TO ALIGN WITH THE SIZE OF OPENING AND
 ZONE EITHER 4 OR 5.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PLEASE PROVIDE TESTING FOR CODE COMPLIANCE FOR FLOOR
 INSULATION: BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 4A) THE DESIGNER OF RECORD TO VERIFY THE SLAB THICKNESS
 FOR THIS BUILDING. THE SUBMITTED TESTING REPORT ASTM
 E-492 FOR PROFLEX MSC 90 WITH A IMPACT INSULATION CLASS
 IIC OF 68 DB IS WITH A SUSPENDED CEILING OF 5/8 INCH
 TYPE X DRYWALL ATTACHED TO A SUSPENDED RIGID X CEILING
 FRAME AND 3 1/2INCHES OF INSULATION. THE TEST HAS TO BE
 WITH THE TILE, THIN SET, SOUND UNDERLAYMENT AND
 ADHESIVE AND CONCRETE SLAB.
  
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 4B) THE SUBMITTED TESTING REPORT ASTM E-90 FOR PROFLEX
 MSC 90 WITH ASOUND TRANSMISSION CLASS OF STC= 72 DB FOR
 PROFLEX MSC 90 IS WITH A SUSPENDED CEILING OF 5/8 INCH
 TYPE X DRYWALL ATTACHED TO A SUSPENDED RIGID X CEILING
 FRAME AND 3 1/2INCHES OF INSULATION. THE TEST HAS TO BE
 WITH THE TILE, THIN SET, SOUND UNDERLAYMENT AND
 ADHESIVE AND CONCRETE SLAB.
  
 FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) COMPLIED. FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  