2015-05-27 09:43:07 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15041065 |
| ADD: 529 S. FLAGLER DR. SUITE # 18-H |
| CONT: CAMBRIDGE CONSTRUCTION |
| TEL: (561)784-3722 |
| E-MAIL:[email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| |
| NOTICE:!!!!!!!!!!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B) |
| FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL |
| IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF |
| PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED |
| FAILURE TO CORRECT A CODE VIOLATION. |
| |
| |
| |
| 2ND REVIEW |
| DATE: MON. MAY 27/2015 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. A NEW FLOOR PLANS WAS SUBMITTED WITH |
| THE ARCHITECT OF RECORDS OWN SEAL, BUT THE SHEETS 1 OF |
| 2 FOR WINDOW PLACEMENT, CUSTOM MULLION AND WIND DESIGN |
| NOT REPLACED, STILL HAS THE CERTIFICATE OF |
| AUTHORIZATION SEAL. L DESIGN FOR WIND BY RAYOMND |
| CHLADNY ARCHITECT, NOTE THE DESIGNER OF RECORD SEALED |
| THE PLANS WITH HIS AA CERTIFICATE OF AUTHORITY SEAL. 61 |
| G 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000 THE |
| PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT OR |
| INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD |
| AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS |
| CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT. |
| DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE |
| RESPONSIBLE ARCHITECT |
| |
| 2) 2ND REQUEST. PLEASE NOTE THE WIND DESIGGN CRITERIA |
| WAS PROVIDED, WHAT WAS NOT PROVIDED WAS THE SIZE OF THE |
| WINDOWS AND DOORS NOR WHERE ZONE 4 AND 5 START AND END. |
| THE PRESSUES NEED TO ALIGN WITH THE SIZE OF OPENING AND |
| ZONE EITHER 4 OR 5. PLEASE PROVIDE THE ACTUAL SIZES OF |
| THE WINDOWS AND SLIDERS TO BE INSTALLED. NOTE, FOR THE |
| SLIDDING GLASS DOORS, IDENTIFY THE SIZES OF PANELS |
| LOCATED ON SHEET 7 OF THE PRODUCT APPROVAL. CIRCLE THE |
| SIZE OF THE PANEL, TYPE OF GLAZING, AND SILL HEIGHT |
| THAT GOVERNS EACH CHART. |
| |
| |
| 3) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) 2ND REVIEW SUPER SAM 125 SALES BROCHURE WAS |
| SUBMITTED, NO TESTING, SUPER SAM 125 HAS A IIC RATING |
| OF 49, MINIMUM REQUIRED IS 50. PLEASE PROVIDE TESTING |
| FOR CODE COMPLIANCE FOR FLOOR INSULATION: BLDG TYPE: |
| TYPE I/ TYPE II FLOOR INSULATION |
| |
| 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 5) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 703.4 NONCOMBUSTIBILITY TESTS. |
| THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 703.4.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 703.4.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: A FLOOR PLAN. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |