2015-05-04 15:55:33 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15041065 |
| ADD: 529 S. FLAGLER DR. SUITE # 18-H |
| CONT: CAMBRIDGE CONSTRUCTION |
| TEL: (561)784-3722 |
| E-MAIL:[email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. MAY 04/2015 |
| ACTION: DENIED |
| |
| IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE. |
| |
| 1) DESIGN FOR WIND BY RAYOMND CHLADNY ARCHITECT, NOTE |
| THE DESIGNER OF RECORD SEALED THE PLANS WITH HIS AA |
| CERTIFICATE OF AUTHORITY SEAL. 61 G 1-16.003 USES OF |
| SEAL. EFFECTIVE 04/18/2000 THE PERSONAL SEAL, SIGNATURE |
| AND DATE OF THE ARCHITECT OR INTERIOR DESIGNER SHALL |
| APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN |
| DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND SHALL BE |
| CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS CORPORATION. |
| A CORPORATE SEAL ALONE IS INSUFFICIENT. DOCUMENTS SHALL |
| BE SIGNED PERSONALLY AND SEALED BY THE RESPONSIBLE |
| ARCHITECT |
| |
| 2) PLEASE NOTE THE WIND DESIGGN CRITERIA WAS PROVIDED, |
| WHAT WAS NOT PROVIDED WAS THE SIZE OF THE WINDOWS AND |
| DOORS NOR WHERE ZONE 4 AND 5 START AND END. |
| THE PRESSUES NEED TO ALIGN WITH THE SIZE OF OPENING AND |
| ZONE EITHER 4 OR 5. |
| |
| |
| 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) PLEASE PROVIDE TESTING FOR CODE COMPLIANCE FOR FLOOR |
| INSULATION: BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| |
| 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 5) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 703.4 NONCOMBUSTIBILITY TESTS. |
| THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 703.4.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 703.4.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: A FLOOR PLAN. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |