Plan Review Notes For Permit 15041044 |
Permit Number |
15041044 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-04 13:15:59 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | COMMENTS: | | | | 1) INDICATE THE SIZE OF THE EXISTING MAIN BREAKER | | PROVIDING THE OVERCURRENT PROTECTION TO THE FEEDER TO | | THE NEW PANEL IN COMPLIANCE WITH THE NEC 408.30 | | ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THE | | MINIMUM FEEDER CAPACITY REQUIRED FOR THE LOAD | | CALCULATED IN ACCORDANCE WITH PARTS II, III, IV, OR V | | OF ARTICLE 220 AS APPLICABLE. | | | | 2) VERIFY OR INSTALL INTERCONNECTED SMOKE DETECTORS IN | | COMPLIANCE WITH THE FBC-R 314-315. | | WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314 AND 315. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|