Plan Review Notes For Permit 15041044
Permit Number 15041044
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-04 13:15:59REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INDICATE THE SIZE OF THE EXISTING MAIN BREAKER
 PROVIDING THE OVERCURRENT PROTECTION TO THE FEEDER TO
 THE NEW PANEL IN COMPLIANCE WITH THE NEC 408.30
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THE
 MINIMUM FEEDER CAPACITY REQUIRED FOR THE LOAD
 CALCULATED IN ACCORDANCE WITH PARTS II, III, IV, OR V
 OF ARTICLE 220 AS APPLICABLE.
  
 2) VERIFY OR INSTALL INTERCONNECTED SMOKE DETECTORS IN
 COMPLIANCE WITH THE FBC-R 314-315.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  