Plan Review Notes
Plan Review Notes For Permit 15041011
Permit Number 15041011
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-28 20:11:505/28/2015
 PROJECT: GLUE PRODUCTS
 PERMIT#: 15041011
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE
 WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER
 DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 ELECTRICAL
  
 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL
 PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC
 408.4
  
 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR
 AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN FBC-ENERGY
 CONSERVATION SECTIONS 505 ELECTRICAL POWER & LIGHTING
 SYSTEMS (MANDATORY).
  
 4. INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL
 EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT.
 NEC 110.26 (D)
  
 5. VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16
  
 6. INDICATE ALL REQUIRED EMERGENCY ILLUMINATION.
 EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS
 OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL
 OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED
 ILLUMINATION. NEC 700.16(F)
  
 7. PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT
 WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS.
 NEC 210.63, 210.8(A)(3), NEC 440.14
  
 8. INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT
 AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A)
  
 SEPARATE ELECTRICAL PERMIT ACCOMPANIED BY
 MANUFACTURER'S EQUIPMENT SUBMITTALS REQUIRED FOR
 ELECTRICAL WORK
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353,
 561-805-7943 OR [email protected]
  