Plan Review Notes
Plan Review Notes For Permit 15041000
Permit Number 15041000
Review Stop P
Sequence Number 1
Notes
Date Text
2015-05-26 15:18:551) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES IS SHOWN
 AS 30 PERSONS. WHERE DID THIS NUMBER COME FROM? THE
 PLAN SHOWS 97 OCUPANTS JUST FOR THE SALES AREA.
 CLARIFY. NOTE: THE FIXTURE COUNT THAT IS NOTED IS
 CORRECT.PLEASE CORRECT THE NUMBER OF PERSONS.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 2) SHT. A1.00 DELETE THE DIAGRAM FOR A PARALLEL
 APPROACH FOR THE DRINKING FOUNTAIN. A FORWARD APPROACH
 IS THE ONLY TYPE PER MITTED EXCEPT IN CHILDREN'S
 FACILITIES. FAC SEC.602.2.
 3) SHT. A8.01, DETAIL #5 - SHOW THE WIDTH OF BOTH
 TOILET ROOMS. A MINIMUM OF 85 INCHES IF BUILT PERFECT,
 86 INCHES ALLOWS FOR CONSTRUCTION TOLERANCES.
 4) SHT. A8.01 - THE ELEVATION DETAIL SHOWS A DIMENSION
 OF 39" - 41". WHAT IS THIS DIMENSION FOR? NOTHING IS
 NOTED.CLARIFY.
 5) SHOW THE HEIGHT DIMENSION OF THE GRAB BAR FROM THE
 FINISH FLOOR. COMPLY W/ FAC SEC. 609.4. THE GRAB BARS
 SHALL BE MEASURED TO THE HEIGHT OF THE GRIPPING
 SURFACE.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  