Plan Review Notes For Permit 15041000 |
Permit Number |
15041000 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-26 15:18:55 | 1) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES IS SHOWN | | AS 30 PERSONS. WHERE DID THIS NUMBER COME FROM? THE | | PLAN SHOWS 97 OCUPANTS JUST FOR THE SALES AREA. | | CLARIFY. NOTE: THE FIXTURE COUNT THAT IS NOTED IS | | CORRECT.PLEASE CORRECT THE NUMBER OF PERSONS.WPB AMEND. | | TO 2010 FBC SEC. 107.2.1. | | 2) SHT. A1.00 DELETE THE DIAGRAM FOR A PARALLEL | | APPROACH FOR THE DRINKING FOUNTAIN. A FORWARD APPROACH | | IS THE ONLY TYPE PER MITTED EXCEPT IN CHILDREN'S | | FACILITIES. FAC SEC.602.2. | | 3) SHT. A8.01, DETAIL #5 - SHOW THE WIDTH OF BOTH | | TOILET ROOMS. A MINIMUM OF 85 INCHES IF BUILT PERFECT, | | 86 INCHES ALLOWS FOR CONSTRUCTION TOLERANCES. | | 4) SHT. A8.01 - THE ELEVATION DETAIL SHOWS A DIMENSION | | OF 39" - 41". WHAT IS THIS DIMENSION FOR? NOTHING IS | | NOTED.CLARIFY. | | 5) SHOW THE HEIGHT DIMENSION OF THE GRAB BAR FROM THE | | FINISH FLOOR. COMPLY W/ FAC SEC. 609.4. THE GRAB BARS | | SHALL BE MEASURED TO THE HEIGHT OF THE GRIPPING | | SURFACE. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|