Plan Review Notes
Plan Review Notes For Permit 15041000
Permit Number 15041000
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-01 15:06:32PLAN DENIED
 1) PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS
 PER TABLE 403.3 FBC (M) 2010
 2) ABANDONED EQUIPMENT MUST BE REMOVED FROM THE
 ROOF AND SEAL CURB WATER TIGHT
 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE
 EXHAUST FAN CURB TO ROOF AND FAN TO CURB, PROVIDE
 TYPE AND SIZE OF ANCHOR USED. PER SECTION
 301.12 WIND RESISTANCE FBC (M) 2010
 4) REFER TO SECTION 503.2.5.4 SHUT OFF
 DAMPER CONTROLS FOR FRESH AIR. 2010
 FLORIDA ENERGY CODE
 5) PROVIDE ENERGY CALCULATIONS PER SECTION
 503.2.1 FLORIDA ENERGY CODE 2010
  