2015-06-01 15:06:32 | PLAN DENIED | | 1) PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS | | PER TABLE 403.3 FBC (M) 2010 | | 2) ABANDONED EQUIPMENT MUST BE REMOVED FROM THE | | ROOF AND SEAL CURB WATER TIGHT | | 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | EXHAUST FAN CURB TO ROOF AND FAN TO CURB, PROVIDE | | TYPE AND SIZE OF ANCHOR USED. PER SECTION | | 301.12 WIND RESISTANCE FBC (M) 2010 | | 4) REFER TO SECTION 503.2.5.4 SHUT OFF | | DAMPER CONTROLS FOR FRESH AIR. 2010 | | FLORIDA ENERGY CODE | | 5) PROVIDE ENERGY CALCULATIONS PER SECTION | | 503.2.1 FLORIDA ENERGY CODE 2010 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|