Plan Review Notes
Plan Review Notes For Permit 15040958
Permit Number 15040958
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-16 15:33:435/16/2015
 PROJECT: 330 FRANKLIN RD
 PERMIT#: 15040958
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 NO ELECTRICAL PLANS HAVE BEEN SUBMITTED WITH THIS
 APPLICATION. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME.
  
 1) THE ARCHITECTUAL PLANS SUBMITTED WITH THIS
 APPLICATION INDICATE THE INSTALLATION OF SEVERAL
 ELECTRICAL ELEMENTS ASSOCIATED WITH THE RENOVATION OF A
 KITCHEN AND BATHROOM OF AN EXISTING SINGLE FAMILY
 DWELLING. PROVIDE COMPLETE ELECTRICAL PLANS DETALAILING
 THE INSTALLATION OR RENNOVATION OF THESE ELEMENTS
 INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
  
 2) A PANEL SCHEDULE INDICATING THE ALL CIRCUIT NUMBERS
 AND CORRESPONDING OCPD AND WRE SIZES. NEC 408.4
  
 3) ALL ELEMENTS INVOLVED IN THE RENOVATION INDICATED ON
 A FLOOR PLAN WITH CIRCUIT NUMBERS CORRESPONDING TO THE
 PANEL SCHEDULE. WPB AMENDMENTS TO FBC 107.3.5.1.2
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 5) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. NEC 210.52 (D)
  
 6) RECEPTACLE OUTLETS SHALL BE LOCATED ON BRANCH
 CIRCUITS IN ACCORDANCE WITH PART III OF ARTICLE 210.
 GENERAL INSTALLATION REQUIREMENTS SHALL BE IN
 ACCORDANCE WITH 406.3(A) THROUGH (F). (D) REPLACEMENT
 OF RECEPTACLES SHALL COMPLY WITH 406.3(D)(1),(2), AND
 (3) AS APPLICABLE. NEC 406.3
  
 7) IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, LIVING
 ROOM, PARLOR, LIBRARY, DEN, SUNROOM, BEDROOM,
 RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING
 UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN NEC
 210.52(A)(1) THROUGH (A)(3).
  
 8) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.NEC 210.52(C)(1)
  
 9) INDICATE AND PROVIDE OR VERIFY ALL REQUIRED SMOKE
 AND/OR CARBON MONOXIDE DETECTORS. FBC-R 314-315
  
 ONCE ELECTRICAL PLANS HAVE BEEN SUBMITTED AND A REVIEW
 CAN BE COMPLETED ADDITIONAL ELERICAL REVIEW
 DEFICIENCIES MAY BE FOUND.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  