Plan Review Notes For Permit 15040884 |
Permit Number |
15040884 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-24 06:39:09 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE POOL HEATER. THE POOL HEATER | | SHALL BE LISTED AND LABELED PER THE 2010 FBCR SEC.G | | 2404.3. | | 2) PER TABLE G2413.4 (1 ), THE MINIMUM SIZE PIPE | | SUPPLYING A 400,000 BTU APPLIANCE SHALL BE A MIN. OF | | 1".THE DRAWING YOU SUBMITTED SHOWS THE PIPING AS 1" AT | | THE METER AND REDUCING TO 3/4". IT SHALL REMAIN 1" TO | | THE APPLIANCE. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|