2015-04-24 06:39:091) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATER. THE POOL HEATER
 SHALL BE LISTED AND LABELED PER THE 2010 FBCR SEC.G
 2404.3.
 2) PER TABLE G2413.4 (1 ), THE MINIMUM SIZE PIPE
 SUPPLYING A 400,000 BTU APPLIANCE SHALL BE A MIN. OF
 1".THE DRAWING YOU SUBMITTED SHOWS THE PIPING AS 1" AT
 THE METER AND REDUCING TO 3/4". IT SHALL REMAIN 1" TO
 THE APPLIANCE.
  