2015-05-15 10:54:25 
 1ST REVIEW: FBC 2010 MECHANICAL
 CHRISTOPHER COLE
  
 1) PROVIDE SHEET M0.1. IT WAS NOT ENCLOSED WITH THE
 SUBMITTED PLAN SETS.
 2) PROVIDE SIZING CALCULATIONS FOR THE FCU'S AND 1.5
 TON SPLIT SYSTEM- SECTION 505.2.2 FBC-10 ENERGY
 CONSERVATION.
 3) INDICATE THE MAKE AND MANUFACTURER OF THE DS
 DETECTORS ON THE PLAN, AND CLARIFY HOW THEY WILL BE
 SUPERVISED PER SECTION 606.4.1 FMC-10.
 4) PROVIDE TYPICAL DETAILS FOR SUPPORT AND HANGING OF
 THE FCU'S, AHU-1, THE DUCTWORK, AND THE CHILLED WATER
 PIPING.
 5) INDICATE THE THICKNESS OF THE CHILLED WATER PIPING
 INSULATIONS- TABLE 503.2.8 FBC-10 ENERGY CONSERVATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  