Plan Review Notes For Permit 15040864 |
Permit Number |
15040864 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-29 10:30:20 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | 1) SHEET A1.1 INDICATES AN INCORRECT REFERENCE TO THE | | FIRE CODE. THE PROPOSED PROJECT SHALL MEET THE | | REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE | | PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 | | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR | | STANDARDS. | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 13, 2010 EDITION. | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2010 EDITION. | | | | 2) SHEET A1.1, A2.1 AND E2.1 ADD ONE (1) EXIT SIGN TO | | LEAD TO THE REAR EXIT ACCESS AND EXIT. | | |
|