2015-05-27 06:53:261) SHT.A0.2 - DEMOLITION NOTE #10 REFERS TO THE REMOVAL
 OF AN EXISTING GAS LINE TO BE CUT AND CAPPED BELOW THE
 EXISTING FLOOR LINE. THIS IS VAGUE AND MORE INFORMATION
 IS REQUIRED. INDICATE ON THE PLAN EXACTLY WHERE THIS
 EXISTING LINE WILL BE REMOVED AND "CAPPED"; PIPING
 CANNOT BE CAPPED OR RUN UNDER A BUILDING SLAB EXCEPT
 WHERE THE INSTALLATION COMPLIES WITH FGC SEC.404.12.
 CLARIFY. SECTION 406.7 OF THE 2010 FUEL GAS CODE
 REQUIRES THAT THE GAS SUPPLY SHALL BE SHUT OFF AND THE
 LINE PRESSURE VENTED TO THE OUTDOORS. THE REMAINING GAS
 IN THE SECTION OF PIPE IS TO BE PURGED WITH AN INERT
 GAS AS REQUIRED BY TABLE 406.7.1.SUBMIT ADDITIONAL
 INFORMATION AND DETAILS AS TO EXACTLY WHAT IS GOING TO
 BE CAPPED, WHERE, HOW, ETC. AIR CANNOT BE USED TO PURGE
 PIPING BECAUSE IT CONTAINS OXYGEN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) SHOW THE DIMENSIONS OF THE NEWLY CREATED SHOWER ON
 SHT. A1.0. THE ROLL -IN SHOWER DIMENSIONS SHALL COMPLY
 WITH FAC SEC.608.2.2.
  