2015-05-14 12:04:52DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN
 REVIEW
  
 APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010
 CHAPTER 1; NEC 2008
 REVIEW CYCLE: 1ST ELECTRICAL REVIEW
 ACTION: FAILED AS INDICATED BELOW:
  
 AS PER FBC 107.2.1 SUBMITTAL DOCUMENT SHOULD BE
 PROPERLY DIMENSIONED AND THOUGH 1/8 SCALE IS
 ACCEPTABLE, IN THIS CASE THE SHEETS APPEAR TO BE VERY
 CLUTTERED TO PROPERLY REVIEW THEM. IN LOOKING THROUGH
 THE SUBMITTAL I NOTICED THAT THE ELECTRICAL RISER
 DIAGRAM IS MISSING ALONG WITH A LIGHTING DIAGRAM. AS
 PART OF THE LIGHTING DIAGRAM I WILL NEED TO HAVE A
 LEGIBLE FIXTURE (LUMINAIRE) SCHEDULE TO BE ABLE TO
 CHECK FOR EMERGENCY AND EXIT LIGHTING COMPLIANCE. I DID
 NOTICE THAT THERE IS NO EXIT LIGHTS ON THE ROOF
 THERE IS A REFERENCE TO ELECTRICAL PAGE E4.1 WHICH IS
 MISSING. I WAS ALSO ABLE TO NOTICE THAT THE HVAC
 EQUIPMENT IS MISSING THE SERVICE OUTLET REQUIRED BY NEC
 210.63
  
  
  