2015-04-22 18:52:59 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEE PAGE 6 OF THE PRODUCT APPROVAL. CONTRACTOR HAS | | PROVIDED THE FASTENING FOR "OPEN" ENCLOSURE. FOR AN | | ENCLOSED STRUCTURE, FASTENING SHOULD BE ACCORDING TO | | THE CHART FOR "ENCLOSED" (PAGE NOT INCLUDED). THIS PAGE | | IS FOR SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, | | BONDED ROOF COVER. | | | | PAGE 9 WAS ALSO PROVIDED, SYSTEM TYPE D: INSULATION, | | MECHANICALLY ATTACHED BASE, BONDED ROOF COVER. | | | | IT IS NOT CLEAR WHICH OF THE TWO SYSTEMS IS PROPOSED. | | PLEASE SELECT ONE. IF SYSTEM C IS SELECTED, PROVIDE THE | | MISSING PAGE (7) AND REVISE PROPOSED FASTENING TO | | CORRELATE WITH THE PRODUCT APPROVAL (OR CIRCLE ON | | PRODUCT APPROVAL). | | |
|