Date |
Text |
2015-06-21 08:23:04 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15040823 |
| ADD: 625 N. FLAGLER DR. / FOYER/ LOBBY |
| CONT: NORTH AMERICAN AUTOMOTIVE |
| TEL: (772)418-1384 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SUN. JUNE 21/2015 |
| ACTION: DENIED |
| |
| 1-3 COMPLIED. |
| |
| |
| BUILDING PROVISO, DEFERRED SUBMITTAL 4) SHEET A-3 NOTE |
| # 2 SHOWS THE USE OF CURTAINWALL STOREFRONT GLAZING AND |
| DOOR SYSTEM. NO PRODUCT APPROVALS WERE SUBMITTED. |
| PLEASE SHOW COMPLIANCE WITH: |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, |
| |
| BUILDING PROVISO, DEFERRED SUBMITTAL 5) 2010 FBC |
| 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) COMPLIED. SHEET A6 SHOWS STEEL TUBING AND HORIZONTAL |
| MULLIONS IN THE CURTAINWALL SYSTEM. SHEET A8 SEE |
| STRUCTURAL. THE STRUCTURAL SHEET S-3 DOES NOT PROVIDE |
| SIZE OF THE STEEL TUBE AND WELD IS NOT IDENTIFIED. |
| |
| 7)THIS BUILDING IS A HIGHRISE AND REQUIRE A THRESHOLD |
| INSPECTOR. THRESHOLD BUILDING FL S. S. 553.71(7) |
| ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| A) COMPLIED 6/21/15. 109.3.6.1 THRESHOLD INSPECTION |
| PLAN. THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ |
| TYPED) SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE |
| SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| B) COMPLIED 7/07/15. THRESHOLD INSPECTOR: WPB AMENDMENT |
| 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| THRESHLOD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| ISSUANCE WILL TAKE PLACE. CONTACT KEN CONRAD MANAGER OF |
| THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR |
| FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| |
| FORMS E-MAILED TO CONTACT: [email protected] |
| 6/21/2015 |
| |
| C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| D) COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| E) 7/27/2015 COMPLIED. |
| |
| F) NOTE, FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED ONLY (2) SETS WERE SUBMITTED. FOR DIGITAL |
| PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE PERMIT |
| LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT |
| LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH |
| STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS |
| OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE.. |
| |
| G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| |
| 8) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |