2015-05-02 13:28:58 | MECHANICAL PLAN REVIEW |
| W. P. B. PERMIT: 15040823 |
| ADD: 625 N. FLAGLER DR. / FOYER/ LOBBY |
| CONT: NORTH AMERICAN AUTOMOTIVE |
| TEL: (772)418-1384 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. MAY 02/2015 |
| ACTION: DENIED |
| |
| 1) SHEET M2.2 NEEDS TO SHOW ON THE OUTSIDE MAKE UP AIR |
| COMPLIANCE WITH : 2010 FBC-ENERGY 03.2.5.4 SHUTOFF |
| DAMPER CONTROLS. |
| BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE |
| EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN |
| THE SYSTEMS OR SPACES SERVED ARE NOT IN USE. |
| VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF |
| AUTOMATICALLY SHUTTING OFF DURING PREOCCUPANCY BUILDING |
| WARMUP, COOLDOWN, AND SETBACK, EXCEPT WHEN VENTILATION |
| REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR WHEN |
| VENTILATION MUST BE SUPPLIED TO MEET CODE REQUIREMENTS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |