Plan Review Notes For Permit 15040820 |
Permit Number |
15040820 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-24 12:43:24 | ROUTED TO B44 | | | | | 2015-04-24 12:37:17 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | COMMENTS:: | | | | ELECTRICAL PERMIT AND PLANS REQUIRED. THE MINIMAL | | ELECTRICAL INFORMATION PROVIDED IN THIS SUBMITTAL IS | | INADAQUATE. | | PROVIDE THE FOLLOWING ADDITIONAL INFORMATION: | | | | 1) A SITE PLAN INDICATING THE LOCATION OF THE | | ELECTRICAL SERVICE PROPOSED TO FEED THE COSTRUCTION | | TRAILER. | | 2) A RISER DIAGRAM INDICATING THE SIZE AND TYPE OF | | SERVICE MAIN AND WIRE PROPOSED TO FEED THE TRAILER. | | 3) THE METHODS AND MATERIALS PROPOSED TO FEED THE | | TRAILER FROM THE NEW SERVICE EQUIPMENT. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|